Diesel Engine Cooling Radiator Package
Type:
Onshore LNG Plant Hazardous Area Emergency Generator Packages
Location:
Australia
Features:
- QTY of 6 remote mounted engine cooling radiator packages.
- Hazardous area rated.
- Designed to Cyclone / seismic loadings.
- 50 deg C high ambient temperature design with no de-rating.
- 690V Electric motor driven ATEX cooling fans.
- Dual heat exchanger design.
- 2101 kW heat rejection Jacket water circuit.
- 791 kW heat rejection Charge air circuit.
- 316L Stainless steel jacket water circuit header / expansion tank.
- 316L Stainless steel charge air circuit header / expansion tank.
- 316L Stainless steel heat exchanger casings.
- Copper heat exchanger tubes.
- Remote fill and level monitoring.